Date: 2020-02-20 Time: 09:30 AM Report ID: 1001001111110
Property:
4567 Great Street to Be On
Investment City of Choice ON
Customer:
Commercial Investor
Real Estate Professional:

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this building. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this building or building.

Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

In Attendance:
Customer and their agent

Type of building:
Commercial and Residential

Temperature:
Over 50

Weather:
Light Rain

Ground/Soil surface condition:
Wet

Rain in last 3 days:
Yes

Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
1.
The building inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The building inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The building inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors.
1.0 ROOF COVERINGS
Viewed roof covering from: Walked roof
Roof Covering: Roll/Selvage
Comments:
  Rolled asphalt roofing with tarred seams is in good condition.
 
1.0 Picture 1
 
1.1 ROOF FLASHINGS - Comments:
 
  1. Rolled roofing has been used as flashing on parapet roof section.  Sealing agent has cracked and should be re-sealed.
  2. Front pillar metal shield has separated leaving exposed seam at front of pillar.
  3. Gap at flashing where wall drops down.  Recommend sealing with exterior caulking.
 
1.1 Picture 1
1.1 Picture 2
 
1.1 Picture 3
 
1.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS
Chimney (exterior): Masonry
Comments:
  Chimney on right side is in use and has no rain cap.  Rain caps protect brick from water damage.
 
1.3 ROOF DRAINAGE SYSTEMS - Comments:
 
1.4 ROOF STRUCTURE AND ATTIC (report leak signs or condensation)
Roof-Type: Flat
Roof Structure: Not visible
Comments:
 
1.5 MASONRY CHIMNEY - Comments:
  Interior of both flues in masonry chimney
 
1.5 Picture 1
1.5 Picture 2
 
1.6 EXTERIOR ROOF ITEMS - Comments:
 
  1. Lower alley roof for 2nd floor apartment has visible deterioration on rolled asphalt roofing material.
  2. Lower alley 1st floor roof has visible deterioration and blistering of asphalt surface.
 
1.6 Picture 1
1.6 Picture 2
 
1.6 Picture 3
 
The roof of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
2.
The building inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The building inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The building inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The building inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.
2.0 WALL CLADDING FLASHING AND TRIM
Siding Style: Brick
Siding Material: Brick veneer
Comments:
 
2.1 DOORS (Exterior)
Exterior Entry Doors: Wood
Comments:
  Rear exit door from restaurant has broken closure device.
 
2.2 WINDOWS - Comments:
 
  1. 2nd level rear alley has cracked mortar on brick window sills. This should be sealed to prevent further damage.
  2. 2nd level rear alley has wood windows that require maintenance, painting and caulking.
 
2.2 Picture 1
2.2 Picture 2
 
2.2 Picture 3
 
2.3 FOUNDATION WALLS AND MORTAR JOINTS - Comments:
 
2.4 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS
Appurtenance: Sidewalk
Comments:
 
2.5 VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building)
Driveway: Shared access
Comments:
 
2.6 EAVES, SOFFITS AND FASCIAS - Comments:
 
2.7 POLARITY AND GROUNDING OF RECEPTACLES ON EXTERIOR WALLS OF INSPECTED STRUCTURE - Comments:
 
2.8 EXTERIOR CONDITION - Comments:
 
  1. Brick damage on left wall of front entrance steps.
  2. Front window ledge has gap in brick which should be sealed.
  3. Upper front concrete trim has visible cracks.
  4. Rear alley on 2nd level has hole in brick.
 
2.8 Picture 1
2.8 Picture 2
 
2.8 Picture 3
2.8 Picture 4
 
2.9 PARKING AREA - Comments:
 
2.10 FIRE ESCAPES - Comments:
 
The exterior of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
3.
The building Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The building inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The building inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The building inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the building inspector or other persons.
3.0 FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.)
Foundation: Brick
Comments:
 
3.1 WALLS (Structural)
Wall Structure: Wood, Brick
Comments:
 
3.2 COLUMNS OR PIERS
Columns or Piers: Supporting walls, Brick Walls
Comments:
 
3.3 FLOORS (Structural)
Floor Structure: 2 X 8, Wood joists
Comments:
 
3.4 CEILINGS (structural) - Comments:
 
The structure of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
4.
The building inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The building inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The building inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The building inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.
4.0 PLUMBING DRAIN, WASTE AND VENT SYSTEMS
Washer Drain Size: 1 1/2" Diameter (undersized)
Plumbing Waste: Cast iron, ABS
Comments:
 
  1. Rear alley plumbing vent does not extend above roof.
  2. Visible water leak at drain line in basement utility area at back of walkway behind pot room wall.
 
4.0 Picture 1
4.0 Picture 2
 
4.0 Picture 3
 
4.1 PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES
Water Source: Public
Water Filters: None
Plumbing Water Supply (into building): Copper
Plumbing Water Distribution (inside building): Copper
Comments:
 
4.2 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS
Water Heater Power Source: Electric
Comments:
  3 - GSW 184 L hot water tanks and one Giant 38.5 Gal hot water tank.  Tanks are not identified as to destination of water.
 
4.2 Picture 1
4.2 Picture 2
 
4.2 Picture 3
4.2 Picture 4
 
4.3 MAIN WATER SHUT-OFF DEVICE (Describe location) - Comments:
  Main water shut off is located in hydro room in basement.
 
4.3 Picture 1
 
4.4 FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) - Comments:
 
4.5 MAIN FUEL SHUT OFF (Describe Location) - Comments:
  Main fuel supply is located in front sidewalk.  There are individual meters with shut offs in front of hydro room.
 
4.5 Picture 1
4.5 Picture 2
 
4.6 SUMP PUMP - Comments:
  Sump pump does not come on automatically.  When plugged in the pump emptied the pit but would not shut off. Float device is not working.
 
4.6 Picture 1
 
The plumbing in the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant building waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
5(A).
5.0.A CEILING
CEILING: DRYWALL
WALLS: CERAMIC TILE
FLOOR: CERAMIC TILE
DOORS: HOLLOW WOOD
Comments:
 
5.1.A WALLS - Comments:
 
5.2.A FLOOR - Comments:
 
5.3.A DOORS - Comments:
 
5.4.A SHUT OFFS FOR TAPS - Comments:
 
5.5.A SINK CONDITION - Comments:
  Mens vanity and sink
 
5.5.A Picture 1
 
5.6.A TOILET SECURE - Comments:
  Urinals
 
5.6.A Picture 1
 
5.7.A EXHAUST FAN - Comments:
 
5.8.A GFCI OUTLET - Comments:
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
5(B).
5.0.B CEILING
CEILING: DRYWALL
WALLS: CERAMIC TILE
FLOOR: CERAMIC TILE
DOORS: HOLLOW WOOD
Comments:
  Ladies washroom
 
5.0.B Picture 1
 
5.1.B WALLS - Comments:
 
5.2.B FLOOR - Comments:
 
5.3.B DOORS - Comments:
  Bathroom stall door has been damaged and repaired.
 
5.3.B Picture 1
 
5.4.B SHUT OFFS FOR TAPS - Comments:
  Shut offs installed
 
5.4.B Picture 1
 
5.5.B SINK CONDITION - Comments:
  Sinks and vanity
 
5.5.B Picture 1
 
5.6.B TOILET SECURE - Comments:
  3 toilets
 
5.6.B Picture 1
5.6.B Picture 2
 
5.6.B Picture 3
 
5.7.B EXHAUST FAN - Comments:
 
5.8.B GFCI OUTLET - Comments:
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
5(C).
5.0.C CEILING
CEILING: DRYWALL
WALLS: DRYWALL & PANELING
FLOOR: CONCRETE
DOORS: HOLLOW WOOD
Comments:
  Staff mens room had no working light.  Bulb maybe broken.
 
5.0.C Picture 1
 
5.1.C WALLS - Comments:
  Paneling rotted along floor beside toilet
 
5.2.C FLOOR - Comments:
 
5.3.C DOORS - Comments:
  Door frame split at lock area
 
5.3.C Picture 1
 
5.4.C SHUT OFFS FOR TAPS - Comments:
 
5.5.C SINK CONDITION - Comments:
  Drain line attached and discharging into sink
 
5.6.C TOILET SECURE - Comments:
  Water was shut off to toilet and tank lid missing.
 
5.7.C EXHAUST FAN - Comments:
 
5.8.C GFCI OUTLET - Comments:
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
5(D).
5.0.D CEILING
CEILING: DRYWALL
WALLS: PANELING
FLOOR: CONCRETE
DOORS: HOLLOW WOOD
Comments:
  Staff  women's bathroom
 
5.0.D Picture 1
 
5.1.D WALLS - Comments:
  Panel on wall is rotted at bottom
 
5.1.D Picture 1
 
5.2.D FLOOR - Comments:
 
5.3.D DOORS - Comments:
  Latch bolt on door
 
5.4.D SHUT OFFS FOR TAPS - Comments:
  One tap for sink is not working.
 
5.5.D SINK CONDITION - Comments:
 
5.6.D TOILET SECURE - Comments:
 
5.7.D EXHAUST FAN - Comments:
 
5.8.D GFCI OUTLET - Comments:
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
6(A).
6.0.A CEILING
CEILING MATERIAL: DRYWALL
WALLS: DRYWALL AND BRICK
FLOORS: VINYL TILES
WINDOWS: WOOD THERMAL SINGLE SASH
Comments:
  Front bar and eating area
 
6.0.A Picture 1
6.0.A Picture 2
 
6.1.A WALLS - Comments:
 
6.2.A FLOORS - Comments:
 
6.3.A WINDOWS - Comments:
  Electric baseboard heaters under front windows tested and working.
 
6.4.A DOORS - Comments:
 
6.5.A OUTLETS AND WALL SWITCHES - Comments:
 
6.6.A SMOKE DETECTORS - Comments:
 
6.7.A SINKS - Comments:
 
6.8.A EXHAUST FAN - Comments:
 
6.9.A GFCI OUTLET - Comments:
 
6.10.A STAIRWELLS - Comments:
  There is no door at top of stairs from basement and bottom stair has latch to keep fire rated door open.
 
6.10.A Picture 1
 
6.11.A ELECTRICAL DEFICIENCIES - Comments:
  Un-protected electrical cable on post at front entrance.
 
6.11.A Picture 1
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
6(B).
6.0.B CEILING
CEILING MATERIAL: DRYWALL
WALLS: DRYWALL AND BRICK
FLOORS: LAMINATE
DOORS: METAL EXTERIOR DOOR, WOOD DOOR WITH GLASS PANELS
Comments:
  Rear bar area
 
6.0.B Picture 1
6.0.B Picture 2
 
6.1.B WALLS - Comments:
 
6.2.B FLOORS - Comments:
 
6.3.B WINDOWS - Comments:
 
6.4.B DOORS - Comments:
 
  1. Rear exit door has broken closure device.
  2. Rear door to patio padlocked and opening doors were secured with screws.  No access to patio area.
 
6.4.B Picture 1
6.4.B Picture 2
 
6.5.B OUTLETS AND WALL SWITCHES - Comments:
 
6.6.B SMOKE DETECTORS - Comments:
 
6.7.B SINKS - Comments:
 
6.8.B EXHAUST FAN - Comments:
 
6.9.B GFCI OUTLET - Comments:
 
6.10.B STAIRWELLS - Comments:
  Rear view of basement entrance.  Door was padlocked and could not be accessed.
 
6.10.B Picture 1
 
6.11.B ELECTRICAL DEFICIENCIES - Comments:
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
6(C).
6.0.C CEILING
CEILING MATERIAL: DRYWALL
WALLS: DRYWALL
FLOORS: VINYL TILES
DOORS: HOLLOW WOOD
Comments:
 
6.1.C WALLS - Comments:
  ProTex ll  chemical extinguisher for exhaust hood.  Vent Pro exhaust hood was serviced in 2010.  Hood exhaust tested and working at time of inspection.
 
6.1.C Picture 1
6.1.C Picture 2
 
6.2.C FLOORS - Comments:
 
  1. Frymaster, Garland and MKE gas range protected by hood.
  2. Blodgett Oven
  3. Commercial dishwasher
  4. Floor is damaged and spongy beside small sink and cooler.
 
6.2.C Picture 1
6.2.C Picture 2
 
6.2.C Picture 3
6.2.C Picture 4
 
6.3.C WINDOWS - Comments:
 
6.4.C DOORS - Comments:
  Compressor unit for cooler is located above kitchen entrance.
 
6.4.C Picture 1
 
6.5.C OUTLETS AND WALL SWITCHES - Comments:
 
6.6.C SMOKE DETECTORS - Comments:
 
6.7.C SINKS - Comments:
  Sink and food prep area
 
6.7.C Picture 1
6.7.C Picture 2
 
6.8.C EXHAUST FAN - Comments:
  Exhaust fan
 
6.8.C Picture 1
 
6.9.C GFCI OUTLET - Comments:
 
6.10.C STAIRWELLS - Comments:
 
6.11.C ELECTRICAL DEFICIENCIES - Comments:
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
7(A).
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
7.0.A LIVING ROOM
Fridge: Viking
Comments:
  Living room
 
7.0.A Picture 1
 
7.1.A CEILINGS - Comments:
 
7.2.A WALLS - Comments:
 
7.3.A FLOORS - Comments:
 
7.4.A OUTLETS AND WALL SWITCHES - Comments:
 
7.5.A DOORS (REPRESENTATIVE NUMBER)
Interior Doors: Hollow core, French
Comments:
  Rear exit door has loose and damaged weather strip.
 
7.6.A WINDOWS (REPRESENTATIVE NUMBER)
Window Types: Single Pane Aluminum Sliders
Comments:
 
7.7.A BEDROOM - Comments:
  Two bedrooms.  Bedroom window frame has chain anchored for exterior light
 
7.7.A Picture 1
7.7.A Picture 2
 
7.7.A Picture 3
 
7.8.A CEILING - Comments:
 
7.9.A WALLS - Comments:
 
7.10.A FLOOR - Comments:
 
7.11.A DOORS - Comments:
 
7.12.A OUTLETS AND WALL SWITCHES - Comments:
 
7.13.A KITCHEN - Comments:
  Kitchen
 
7.13.A Picture 1
 
7.14.A CEILING - Comments:
 
7.15.A WALLS - Comments:
 
7.16.A WINDOWS - Comments:
 
7.17.A FLOOR - Comments:
 
7.18.A COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS - Comments:
  Tap control unit is loose on sink in kitchen
 
7.19.A SHUT OFFS FOR TAPS - Comments:
 
7.20.A PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT - Comments:
 
7.21.A APPLIANCE SERIAL NUMBERS - Comments:
  Appliance serial numbers
 
7.21.A Picture 1
7.21.A Picture 2
 
7.22.A REFRIGERATOR - Comments:
 
7.23.A RANGES/OVENS/COOKTOPS
Range/Oven: WHITE WESTINGHOUSE
Comments:
 
7.24.A RANGE HOOD
Exhaust/Range hood: VENTED, BROAN
Comments:
 
7.25.A HEATING EQUIPMENT
Heat Type: Hot Water Radiators
Comments:
  Hot water radiators are heat source for apartment.
 
7.26.A PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM - Comments:
 
7.27.A LOCATION OF MAIN AND DISTRIBUTION PANELS
Panel capacity: 125 AMP
Panel Type: Circuit breakers
Comments:
  125 amp Cutler Hammer sub panel is on wall outside of kitchen area.
 
7.27.A Picture 1
 
7.28.A OUTLETS AND WALL SWITCHES - Comments:
  Right side purple bedroom has loose outlet on front corner.
 
7.29.A SMOKE DETECTORS - Comments:
 
7.30.A STEPS, STAIRWAYS, BALCONIES AND RAILINGS - Comments:
 
7.31.A BATHROOM - Comments:
 
7.32.A SINK - Comments:
  Sink
 
7.32.A Picture 1
 
7.33.A BATHTUB - Comments:
  Shower unit
 
7.33.A Picture 1
 
7.34.A GFCI OUTLET - Comments:
 
7.35.A TOILET - Comments:
 
7.36.A CEILING - Comments:
  Damage to drywall over sink in apt #1
 
7.36.A Picture 1
 
7.37.A WALL - Comments:
 
7.38.A FLOOR - Comments:
 
7.39.A WINDOW - Comments:
 
7.40.A OTHER - Comments:
  Whirlpool washer and dryer serial numbers
 
7.40.A Picture 1
7.40.A Picture 2
 
7.41.A PORCHES OR DECKS - Comments:
 
The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
7(B).
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
7.0.B LIVING ROOM
Fridge: GE
Comments:
  Living and dining room have previous water damage at wall and ceiling joint.
 
7.0.B Picture 1
7.0.B Picture 2
 
7.0.B Picture 3
 
7.1.B CEILINGS - Comments:
 
  1. Front entrance hallway has light which has added electrical cable added to improperly.
  2. Drywall crack in ceiling beside smoke detector.
 
7.1.B Picture 1
7.1.B Picture 2
 
7.2.B WALLS - Comments:
 
7.3.B FLOORS - Comments:
 
7.4.B OUTLETS AND WALL SWITCHES - Comments:
 
7.5.B DOORS (REPRESENTATIVE NUMBER)
Interior Doors: Hollow core
Comments:
 
7.6.B WINDOWS (REPRESENTATIVE NUMBER)
Window Types: Single pane, Single-hung, Thermal/Insulated
Comments:
 
7.7.B BEDROOM - Comments:
  Bedroom
 
7.7.B Picture 1
 
7.8.B CEILING - Comments:
 
7.9.B WALLS - Comments:
 
7.10.B FLOOR - Comments:
 
7.11.B DOORS - Comments:
 
7.12.B OUTLETS AND WALL SWITCHES - Comments:
 
7.13.B KITCHEN - Comments:
  Kitchen
 
7.13.B Picture 1
 
7.14.B CEILING - Comments:
 
7.15.B WALLS - Comments:
 
7.16.B WINDOWS - Comments:
 
7.17.B FLOOR - Comments:
 
7.18.B COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS - Comments:
 
7.19.B SHUT OFFS FOR TAPS - Comments:
 
7.20.B PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT - Comments:
 
7.21.B APPLIANCE SERIAL NUMBERS - Comments:
  Appliance serial numbers
 
7.21.B Picture 1
7.21.B Picture 2
 
7.22.B REFRIGERATOR - Comments:
 
7.23.B RANGES/OVENS/COOKTOPS
Range/Oven: GENERAL ELECTRIC, GAS
Comments:
 
7.24.B RANGE HOOD
Exhaust/Range hood: VENTED, NUTONE
Comments:
 
7.25.B HEATING EQUIPMENT
Heat Type: Hot Water Radiators
Comments:
 
7.26.B PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM - Comments:
 
7.27.B LOCATION OF MAIN AND DISTRIBUTION PANELS
Panel capacity: 100 AMP
Panel Type: Fuses
Comments:
 
  1. Electrical panel is located in  bedroom closet.
  2. Panel has two double tap connections. Two wires on one circuit screw.  Only one permitted.
  3. Hole in drywall above panel exposing electrical cable.
 
7.27.B Picture 1
7.27.B Picture 2
 
7.27.B Picture 3
 
7.28.B OUTLETS AND WALL SWITCHES - Comments:
 
7.29.B SMOKE DETECTORS - Comments:
 
7.30.B BATHROOM - Comments:
 
7.31.B SINK - Comments:
  Sink counter has some separating laminate at side rail
 
7.31.B Picture 1
 
7.32.B BATHTUB - Comments:
  Bathtub
 
7.32.B Picture 1
 
7.33.B GFCI OUTLET - Comments:
 
7.34.B TOILET - Comments:
  Toilet is loose and should be re-secured to prevent water leakage.
 
7.35.B CEILING - Comments:
 
7.36.B WALL - Comments:
 
7.37.B FLOOR - Comments:
  Hall floor drops at entrance to bathroom
 
7.38.B WINDOW - Comments:
 
7.39.B OTHER - Comments:
 
    1. Porch has been extended and windows added. Floor drops at entrance.

 

 
7.39.B Picture 1
 
7.40.B PORCHES OR DECKS - Comments:
 
  1. Wood walkway to Unit #2 has no guards or safety devices.
  2. Exterior wood window exterior trim in this area is cracked and soft.  Maintenance and painting is required.
  3. Hole in brick over kitchen window.
  4. Deck boards are rotting in areas.
 
7.40.B Picture 1
7.40.B Picture 2
 
7.40.B Picture 3
7.40.B Picture 4
 
7.40.B Picture 5
 
The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
7(C).
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
7.0.C LIVING ROOM
Fridge: GE
Comments:
  Living and dining room
 
7.0.C Picture 1
7.0.C Picture 2
 
7.1.C CEILINGS - Comments:
 
7.2.C WALLS - Comments:
 
7.3.C FLOORS - Comments:
  Floors squeak through out apartment.  Hard wood flooring
 
7.4.C OUTLETS AND WALL SWITCHES - Comments:
 
7.5.C DOORS (REPRESENTATIVE NUMBER)
Interior Doors: Hollow core
Comments:
 
7.6.C WINDOWS (REPRESENTATIVE NUMBER)
Window Types: Single-hung, Thermal/Insulated
Comments:
 
7.7.C BEDROOM - Comments:
  Bedroom and office. 
 
7.7.C Picture 1
7.7.C Picture 2
 
7.8.C CEILING - Comments:
 
7.9.C WALLS - Comments:
 
7.10.C FLOOR - Comments:
  Bedroom has area of hardwood flooring that has been replaced.

 

 
7.10.C Picture 1
 
7.11.C DOORS - Comments:
  Office door doesn't latch.  Requires striker plate adjustment
 
7.12.C OUTLETS AND WALL SWITCHES - Comments:
 
7.13.C KITCHEN - Comments:
  Kitchen
 
7.13.C Picture 1
 
7.14.C CEILING - Comments:
 
7.15.C WALLS - Comments:
 
7.16.C WINDOWS - Comments:
 
7.17.C FLOOR - Comments:
 
7.18.C COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS - Comments:
 
7.19.C SHUT OFFS FOR TAPS - Comments:
 
7.20.C PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT - Comments:
 
7.21.C APPLIANCE SERIAL NUMBERS - Comments:
  Appliance serial numbers
 
7.21.C Picture 1
7.21.C Picture 2
 
7.22.C REFRIGERATOR - Comments:
 
7.23.C RANGES/OVENS/COOKTOPS
Range/Oven: BEAUMARK
Comments:
 
7.24.C RANGE HOOD
Exhaust/Range hood: RE-CIRCULATE, NUTONE
Comments:
 
7.25.C HEATING EQUIPMENT
Heat Type: Hot Water Radiators
Comments:
 
7.26.C PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM - Comments:
 
7.27.C LOCATION OF MAIN AND DISTRIBUTION PANELS
Panel capacity: 100 AMP
Panel Type: Fuses
Comments:
  Electrical panel is located in kitchen storage cupboard. Panel is Amalgamated 100 amp with copper wire.
 
7.27.C Picture 1
7.27.C Picture 2
 
7.28.C OUTLETS AND WALL SWITCHES - Comments:
 
7.29.C SMOKE DETECTORS - Comments:
 
7.30.C BATHROOM - Comments:
 
7.31.C SINK - Comments:
  Sink and toilet
 
7.31.C Picture 1
 
7.32.C BATHTUB - Comments:
  Bathtub has cracked grout on shower wall.
 
7.32.C Picture 1
7.32.C Picture 2
 
7.33.C GFCI OUTLET - Comments:
 
7.34.C TOILET - Comments:
 
7.35.C CEILING - Comments:
 
7.36.C WALL - Comments:
 
7.37.C FLOOR - Comments:
 
7.38.C WINDOW - Comments:
 
7.39.C PORCHES OR DECKS - Comments:
 
  1. Rear alley entrance.   Hole in brick wall beside window.
  2. Loose guards on balcony portion of entrance.
  3. Side entrance door has broken closure device.
  4. Apt 3 dryer vent is not flush or sealed against masonry.
  5. Deck boards on walkway area are rotted.

 

 
7.39.C Picture 1
7.39.C Picture 2
 
7.39.C Picture 3
7.39.C Picture 4
 
7.39.C Picture 5
 
The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
7(D).
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.
7.0.D LIVING ROOM
Fridge: McClary
Comments:
  Living and dining area
 
7.0.D Picture 1
7.0.D Picture 2
 
7.1.D CEILINGS - Comments:
 
7.2.D WALLS - Comments:
 
7.3.D FLOORS - Comments:
 
7.4.D OUTLETS AND WALL SWITCHES - Comments:
  Reversed polarity in dining room area
 
7.5.D DOORS (REPRESENTATIVE NUMBER)
Interior Doors: Hollow core
Comments:
 
7.6.D WINDOWS (REPRESENTATIVE NUMBER)
Window Types: Single Pane Aluminum Sliders
Comments:
 
7.7.D BEDROOM - Comments:
  Bedroom
 
7.7.D Picture 1
 
7.8.D CEILING - Comments:
 
7.9.D WALLS - Comments:
 
7.10.D FLOOR - Comments:
 
7.11.D DOORS - Comments:
 
7.12.D OUTLETS AND WALL SWITCHES - Comments:
 
7.13.D KITCHEN - Comments:
  Kitchen
 
7.13.D Picture 1
 
7.14.D CEILING - Comments:
 
7.15.D WALLS - Comments:
 
7.16.D WINDOWS - Comments:
 
7.17.D FLOOR - Comments:
 
7.18.D COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS - Comments:
 
7.19.D SHUT OFFS FOR TAPS - Comments:
 
7.20.D PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT - Comments:
 
7.21.D APPLIANCE SERIAL NUMBERS - Comments:
  Appliance serial numbers
 
7.21.D Picture 1
 
7.21.D Picture 2
 
7.22.D REFRIGERATOR - Comments:
 
7.23.D RANGES/OVENS/COOKTOPS
Range/Oven: GENERAL ELECTRIC, GAS
Comments:
 
7.24.D RANGE HOOD
Exhaust/Range hood: VENTED, NUTONE
Comments:
 
7.25.D HEATING EQUIPMENT
Heat Type: Hot Water Radiators
Comments:
 
7.26.D PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM - Comments:
 
7.27.D LOCATION OF MAIN AND DISTRIBUTION PANELS
Panel capacity: 100 AMP
Panel Type: Fuses
Comments:
  Amalgamated 100 amp panel is located in bedroom closet.
 
7.27.D Picture 1
7.27.D Picture 2
 
7.28.D OUTLETS AND WALL SWITCHES - Comments:
 
7.29.D SMOKE DETECTORS - Comments:
 
7.30.D BATHROOM - Comments:
 
7.31.D SINK - Comments:
  Sink has reversed polarity at outlet.  Recommend having repaired.  Adding GFCI protection is recommended although not required.
 
7.31.D Picture 1
 
7.32.D BATHTUB - Comments:
  Bathtub
 
7.32.D Picture 1
 
7.33.D GFCI OUTLET - Comments:
 
7.34.D TOILET - Comments:
 
7.35.D CEILING - Comments:
 
7.36.D WALL - Comments:
 
7.37.D FLOOR - Comments:
 
7.38.D WINDOW - Comments:
 
7.39.D OTHER - Comments:
 
7.40.D PORCHES OR DECKS - Comments:
  Wood steps up to unit C porch on 3rd floor have the following deficiencies:
  1. Wood steps are rotted.
  2. Supporting post is rotted at top and bottom and is not attached at base.
  3. Window has been filled in but has missing capping and no cap for vinyl siding.
  4. Exterior outlet box is loose and exposed on wall.


 
7.40.D Picture 1
7.40.D Picture 2
 
7.40.D Picture 3
7.40.D Picture 4
 
7.40.D Picture 5
7.40.D Picture 6
 
7.40.D Picture 7
 
The heating and cooling system of this building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
8.
The building inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. The building inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The building inspector shall report any observed aluminum branch circuit wiring. The building inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The building inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment.
8.0 SERVICE ENTRANCE CONDUCTORS
Electrical Service Conductors: Below ground
Comments:
 
8.1 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS
Panel capacity: 400 AMP
Panel Type: Circuit breakers
Comments:
  Grounding connections in front of hydro room are corroded and loose.  Recommend replacement of clamps.
 
8.1 Picture 1
 
8.2 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE
Branch wire 15 and 20 AMP: Copper
Wiring Methods: Romex
Comments:
 
8.3 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) - Comments:
 
  1. Un-used conduit in basement beside fire alarm panel.
  2.  
 
8.3 Picture 1
 
8.4 POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE - Comments:
 
8.5 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) - Comments:
 
8.6 LOCATION OF MAIN AND DISTRIBUTION PANELS - Comments:
  Main electrical shut off is located in basement hydro room
 
8.7 PANELS AND AMPERAGE - Comments:
 
8.8 SMOKE DETECTORS - Comments:
 
  1. Smoke detectors tested and working in all apartments.
  2. Hall smoke detectors are hooked to fire alarm and were not tested.
  3. Restaurant has HAD type detectors also hooked into fire alarm.
 
8.9 CARBON MONOXIDE DETECTORS - Comments:
 
8.10 FIRE ALARM PANEL - Comments:
  Notifier 500 fire alarm panel has cover removed.  System was in trouble and indicated battery was dis-connected.
 
8.10 Picture 1
 
8.11 FIRE PULL STATIONS - Comments:
  Fire alarm pull stations are located at all exits in apartments and restaurant.
 
8.12 EMERGENCY LIGHTING - Comments:
  Emergency lighting tested and working.
 
8.13 EXIT LIGHTS - Comments:
  Exit light at basement washroom area was not working at time of inspection.
 
The electrical system of the building was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
9(A).
9.0.A CEILING
CEILING: DRYWALL
WALLS: PLYWOOD OVER BRICK
FLOOR: CONCRETE
DOORS: FIRE RATED
Comments:
  Hydro room equipment list:
  1. 600 V disconnect for dry transformer.
  2. 400 amp main disconnect for building.
  3. 3 - 37 1/2 KVA transformers  1 - 30 KVA transformer.
  4. Apartments have individual meters
  5. 125 amp Federal Pioneer house meter
  6. 200 amp disconnect for restaurant which feeds panel for convection oven etc.
  7. Restaurant has 200 amp Square D panel box.
 
9.0.A Picture 1
9.0.A Picture 2
 
9.0.A Picture 3
9.0.A Picture 4
 
9.0.A Picture 5
9.0.A Picture 6
 
9.0.A Picture 7
9.0.A Picture 8
 
9.0.A Picture 9
 
9.1.A WALLS - Comments:
 
  1. Exposed wiring in junction box in hydro room
  2. Open junction box on wall.
  3. Loose light fixture.
  4. Open junction box.
 
9.1.A Picture 1
9.1.A Picture 2
 
9.1.A Picture 3
9.1.A Picture 4
 
9.2.A FLOOR - Comments:
 
9.3.A DOORS - Comments:
 
9.4.A FIRE SEPARATION - Comments:
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
9(B).
9.0.B CEILING
CEILING: DRYWALL
WALLS: DRYWALL
FLOOR: CONCRETE
DOORS: FIRE RATED
Comments:
 
  1. Weil-McLain hot water boiler  -  working with no insulation on pipes.
  2. Raypak hot water boiler  - was not working and is hooked up to storage tank -  rental equipment
  3. Pressure Relief Valve is corroded and should be cleaned or replaced.
  4. Valve is broken on line from boiler storage tank.
 
9.0.B Picture 1
9.0.B Picture 2
 
9.0.B Picture 3
 
9.0.B Picture 4
 
9.0.B Picture 5
9.0.B Picture 6
 
9.0.B Picture 7
9.0.B Picture 8
 
9.1.B WALLS - Comments:
 
9.2.B FLOOR - Comments:
 
9.3.B DOORS - Comments:
 
9.4.B FIRE SEPARATION - Comments:
 
  1. Electrical penetrations in boiler area of fire separation.
  2. Hole in front of boiler room wall penetrates fire separation.
 
9.4.B Picture 1
9.4.B Picture 2
 
9.4.B Picture 3
9.4.B Picture 4
 
9.5.B COMBUSTION AIR - Comments:
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
10.
10.0 TYPE OF HEAT
Heat Energy Source: Natural Gas
Type of Heat Equipment: Hot Water Circulating Boiler, Natural Gas Furnaces
Comments:
 
  1. Apartments are heated with hot water radiators.
  2. Restaurant has two forced air natural gas furnaces.
 
10.1 MANUFACTURER - Comments:
  KeepRite
 
10.2 DATE AND SERIAL NUMBER - Comments:
 
10.3 CONDITION OF HEATING SYSTEM - Comments:
 
10.4 LOCATION - Comments:
  Furnaces are located in basement utility area.  Boiler is located in boiler room at front of basement
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
11.
11.0 MANUFACTURER
MAKE OF AIR CONDITIONER: KEEPRITE
NUMBER OF UNITS: 2
Comments:
  Both units are KeepRite
 
11.1 BTU's - Comments:
  Both units are 4 ton capacity.  29.1 amp per unit
 
11.2 MODEL & SERIAL NUMBER - Comments:
  Unit #1  Model  CAC048AKC4  Serial  E053909606

Unit #2  Model  CAC048AKC4  Serial  E053909607

 

 
11.2 Picture 1
11.2 Picture 2
 
11.3 LOCATION - Comments:
  Two central air conditioner units are located on rear of roof.
 
11.3 Picture 1
11.3 Picture 2
 
11.4 DEFICIENCIES - Comments:
  Insulation is missing from compressor line. Recommend adding insulation.
 
11.4 Picture 1
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
12.
12.0 TYPE OF UNIT - Comments:
 
  1. Kitchen exhaust motor and duct system. Older model which has been generally replaced using upblast type of exhaust.
  2. Exhaust fan unit not in use in utility area
 
12.0 Picture 1
 
12.1 LOCATION OF UNIT - Comments:
 
  1. Right side of upper 3rd floor roof.
  2. First floor roof has exhaust duct which discharges onto asphalt roof material.

 

 

 
12.1 Picture 1
12.1 Picture 2
 
12.2 CONDITION OF UNIT - Comments:
  Roof top exhaust unit has loose covers.  Working condition is unknown.
 
12.2 Picture 1
12.2 Picture 2
 
12.2 Picture 3
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
13.
13.0 HANDRAILS - Comments:
  Handrail is loose on front stairwell leading to apartments.
 
13.1 PULL STATIONS - Comments:
 
13.2 EMERGENCY LIGHTS - Comments:
 
13.3 ELECTRICAL - Comments:
  First floor outlet has reversed polarity and cord stapled to wall feeding door bells.
 
13.3 Picture 1
13.3 Picture 2
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
14(A).
14.0.A CEILINGS
CEILING: DRYWALL
WALLS: DRYWALL, UNFINISHED
FLOOR: VINYL TILES
DOORS: HOLLOW WOOD
Comments:
  Side office.  Addon construction
 
14.0.A Picture 1
 
14.1.A WALLS - Comments:
  Rear wall of office has exhaust fan which discharges into hallway.  This is not permitted, discharge has to go outside.
 
14.1.A Picture 1
 
14.2.A FLOOR - Comments:
 
14.3.A DOORS - Comments:
 
14.4.A WINDOWS - Comments:
 
14.5.A FIRE SEPARATION - Comments:
 
14.6.A LIFE SAFETY EQUIPMENT - Comments:
 
14.7.A ELECTRICAL DEFICIENCIES - Comments:
 
  1. Open junction box in ceiling.
  2. Un-secured electrical wire for light switch.
  3. Extension cord material un-secured and no connector used in junction box.
 
14.7.A Picture 1
14.7.A Picture 2
 
14.7.A Picture 3
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
14(B).
14.0.B CEILINGS
CEILING: DRYWALL
WALLS: DRYWALL
FLOOR: CONCRETE
Comments:
  Two KeepRite natural gas furnaces.  2005 models
  1. One furnace filter is damaged and requires replacement.
  2. Furnace closest to exit has loose ground wire from exhaust blower motor.
 
14.0.B Picture 1
14.0.B Picture 2
 
14.0.B Picture 3
 
14.0.B Picture 4
14.0.B Picture 5
 
14.1.B WALLS - Comments:
 
14.2.B FLOOR - Comments:
  Condensate lines for furnaces are not draining into hole in floor.  Hole in floor may not be trapped and could be source for sewer gas to enter building.
 
14.2.B Picture 1
 
14.3.B DOORS - Comments:
 
14.4.B WINDOWS - Comments:
 
14.5.B FIRE SEPARATION - Comments:
 
14.6.B LIFE SAFETY EQUIPMENT - Comments:
  Rear exit door was padlocked and could not be inspected.
 
14.7.B ELECTRICAL DEFICIENCIES - Comments:
 
  1. Un-used electrical cable with taped connections should be removed if not used. 
  2. Open junction box in ceiling.
  3. Open junction box above furnaces
 
14.7.B Picture 1
14.7.B Picture 2
 
14.7.B Picture 3
14.7.B Picture 4
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
14(C).
14.0.C CEILINGS
CEILING: DRYWALL
WALLS: DRYWALL
FLOOR: CONCRETE
DOORS: FIRE RATED
Comments:
  Utility area
 
14.0.C Picture 1
 
14.1.C WALLS - Comments:
  Sign on plumbing about previous flooding of basement.
 
14.1.C Picture 1
 
14.2.C FLOOR - Comments:
 
14.3.C DOORS - Comments:
 
14.4.C WINDOWS - Comments:
 
14.5.C FIRE SEPARATION - Comments:
 
  1. Ceiling in utility area has many holes from wiring penetrations etc.
  2. Area of boiler room has water damaged drywall in ceiling on both sides of fire door.  Wall beside door to boiler room has also been damaged.
 
14.5.C Picture 1
14.5.C Picture 2
 
14.5.C Picture 3
14.5.C Picture 4
 
14.5.C Picture 5
14.5.C Picture 6
 
14.6.C LIFE SAFETY EQUIPMENT - Comments:
 
14.7.C ELECTRICAL DEFICIENCIES - Comments:
 
  1. Electrical outlet under stairs in tool area has open ground and extension cord stapled for use beside outlet.
  2. Small walkway to rear of bldg has un-secured electrical wires from outlet box.
  3. Compressor unit at rear of utility area has open junction box and exposed wiring.
  4. Open junction box in ceiling near boilers room.
  5. Un-used BX cable in ceiling of damaged drywall area.
 
14.7.C Picture 1
14.7.C Picture 2
 
14.7.C Picture 3
14.7.C Picture 4
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
14(D).
14.0.D CEILINGS
CEILING: DRYWALL
WALLS: DRYWALL & PANELING
FLOOR: CONCRETE
DOORS: MISSING
Comments:
 
  1. Basement pot washing room has washer and dryer.
  2. Serial numbers
  3. Exhaust fan missing cover in ceiling.
 
14.0.D Picture 1
 
14.0.D Picture 2
 
14.0.D Picture 3
14.0.D Picture 4
 
14.1.D WALLS - Comments:
 
14.2.D FLOOR - Comments:
 
14.3.D DOORS - Comments:
 
14.4.D WINDOWS - Comments:
 
14.5.D FIRE SEPARATION - Comments:
 
14.6.D LIFE SAFETY EQUIPMENT - Comments:
 
14.7.D ELECTRICAL DEFICIENCIES - Comments:
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
14(E).
14.0.E CEILINGS - Comments:
 
  1. Draft walk-in cooler and cooling unit info
  2. 2nd cooling unit info
  3. HAD's installed in cooler for fire detection
  4. Compressor units for coolers are located in utility area racking beside hot water tanks.
 
14.0.E Picture 1
14.0.E Picture 2
 
14.0.E Picture 3
14.0.E Picture 4
 
14.0.E Picture 5
14.0.E Picture 6
 
14.1.E WALLS - Comments:
 
14.2.E FLOOR - Comments:
 
14.3.E DOORS - Comments:
 
14.4.E WINDOWS - Comments:
 
14.5.E FIRE SEPARATION - Comments:
 
14.6.E LIFE SAFETY EQUIPMENT - Comments:
 
14.7.E ELECTRICAL DEFICIENCIES - Comments:
  Extension cord passes through cooler to 12 v transformer in ceiling.  This is not permitted and permanent wiring should be installed.
 
14.7.E Picture 1
14.7.E Picture 2
 
Top Table of Contents Bottom
IN=Inspected NI=Not Inspected NP=Not Present RR=Repair or Replace 
INNINPRR  
14(F).
14.0.F CEILINGS
CEILING: DRYWALL
WALLS: DRYWALL
FLOOR: CONCRETE
DOORS: HOLLOW WOOD
Comments:
 
14.1.F WALLS - Comments:
 
14.2.F FLOOR - Comments:
 
14.3.F DOORS - Comments:
 
14.4.F WINDOWS - Comments:
 
14.5.F FIRE SEPARATION - Comments:
  No fire separation in rear liquor storage room.  Ceiling has been removed.
 
14.5.F Picture 1
 
14.6.F LIFE SAFETY EQUIPMENT - Comments:
 
14.7.F ELECTRICAL DEFICIENCIES - Comments:
 

Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Orillia Home Inspections
Top Table of Contents Bottom
 

General Summary


Napoleon Home Inspections

Certified Building Code Official

7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255

Customer
Commercial Investor

Address
4567 Great Street to Be On
Investment City of Choice ON

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

1.  Roofing, Roof Structure, Chimneys, and Attic
1.1   ROOF FLASHINGS  
  Inspected  
  1. Rolled roofing has been used as flashing on parapet roof section.  Sealing agent has cracked and should be re-sealed.
  2. Front pillar metal shield has separated leaving exposed seam at front of pillar.
  3. Gap at flashing where wall drops down.  Recommend sealing with exterior caulking.
1.2   SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS  
  Inspected  
Chimney on right side is in use and has no rain cap.  Rain caps protect brick from water damage.
1.6   EXTERIOR ROOF ITEMS  
  Inspected  
  1. Lower alley roof for 2nd floor apartment has visible deterioration on rolled asphalt roofing material.
  2. Lower alley 1st floor roof has visible deterioration and blistering of asphalt surface.

2.  Exterior
2.1   DOORS (Exterior)  
  Inspected  
Rear exit door from restaurant has broken closure device.
2.2   WINDOWS  
  Inspected  
  1. 2nd level rear alley has cracked mortar on brick window sills. This should be sealed to prevent further damage.
  2. 2nd level rear alley has wood windows that require maintenance, painting and caulking.
2.8   EXTERIOR CONDITION  
  Inspected  
  1. Brick damage on left wall of front entrance steps.
  2. Front window ledge has gap in brick which should be sealed.
  3. Upper front concrete trim has visible cracks.
  4. Rear alley on 2nd level has hole in brick.

5(B).  Ladies Washroom
5.3.B   DOORS  
  Inspected  
Bathroom stall door has been damaged and repaired.

5(C).  Staff Men's Room
5.6.C   TOILET SECURE  
  Inspected  
Water was shut off to toilet and tank lid missing.

6(A).  Front Bar Area
6.10.A   STAIRWELLS  
  Inspected  
There is no door at top of stairs from basement and bottom stair has latch to keep fire rated door open.

6(B).  Rear Bar Area
6.4.B   DOORS  
  Inspected  
  1. Rear exit door has broken closure device.
  2. Rear door to patio padlocked and opening doors were secured with screws.  No access to patio area.

6(C).  Kitchen Area
6.2.C   FLOORS  
  Inspected  
  1. Frymaster, Garland and MKE gas range protected by hood.
  2. Blodgett Oven
  3. Commercial dishwasher
  4. Floor is damaged and spongy beside small sink and cooler.

7(A).  Unit #1
7.5.A   DOORS (REPRESENTATIVE NUMBER)  
  Inspected  
Rear exit door has loose and damaged weather strip.
7.7.A   BEDROOM  
  Inspected  
Two bedrooms.  Bedroom window frame has chain anchored for exterior light
7.36.A   CEILING  
  Inspected  
Damage to drywall over sink in apt #1

7(B).  Unit #2
7.0.B   LIVING ROOM  
  Inspected  
Living and dining room have previous water damage at wall and ceiling joint.
7.1.B   CEILINGS  
  Inspected  
  1. Front entrance hallway has light which has added electrical cable added to improperly.
  2. Drywall crack in ceiling beside smoke detector.
7.27.B   LOCATION OF MAIN AND DISTRIBUTION PANELS  
  Inspected  
  1. Electrical panel is located in  bedroom closet.
  2. Panel has two double tap connections. Two wires on one circuit screw.  Only one permitted.
  3. Hole in drywall above panel exposing electrical cable.
7.31.B   SINK  
  Inspected  
Sink counter has some separating laminate at side rail
7.37.B   FLOOR  
  Inspected  
Hall floor drops at entrance to bathroom
7.40.B   PORCHES OR DECKS  
  Inspected  
  1. Wood walkway to Unit #2 has no guards or safety devices.
  2. Exterior wood window exterior trim in this area is cracked and soft.  Maintenance and painting is required.
  3. Hole in brick over kitchen window.
  4. Deck boards are rotting in areas.

7(C).  Unit #3
7.3.C   FLOORS  
  Inspected  
Floors squeak through out apartment.  Hard wood flooring
7.10.C   FLOOR  
  Inspected  
Bedroom has area of hardwood flooring that has been replaced.

 

7.11.C   DOORS  
  Inspected  
Office door doesn't latch.  Requires striker plate adjustment
7.32.C   BATHTUB  
  Inspected  
Bathtub has cracked grout on shower wall.
7.39.C   PORCHES OR DECKS  
  Inspected  
  1. Rear alley entrance.   Hole in brick wall beside window.
  2. Loose guards on balcony portion of entrance.
  3. Side entrance door has broken closure device.
  4. Apt 3 dryer vent is not flush or sealed against masonry.
  5. Deck boards on walkway area are rotted.

 


9(B).  Boiler Room
9.4.B   FIRE SEPARATION  
  Inspected  
  1. Electrical penetrations in boiler area of fire separation.
  2. Hole in front of boiler room wall penetrates fire separation.

12.  Exhaust Units
12.1   LOCATION OF UNIT  
  Inspected  
  1. Right side of upper 3rd floor roof.
  2. First floor roof has exhaust duct which discharges onto asphalt roof material.

 

 


13.  Stair Wells
13.0   HANDRAILS  
  Inspected  
Handrail is loose on front stairwell leading to apartments.

14(C).  Utility Area
14.5.C   FIRE SEPARATION  
  Inspected  
  1. Ceiling in utility area has many holes from wiring penetrations etc.
  2. Area of boiler room has water damaged drywall in ceiling on both sides of fire door.  Wall beside door to boiler room has also been damaged.

14(D).  Pot Washing Room
14.0.D   CEILINGS  
  Inspected  
  1. Basement pot washing room has washer and dryer.
  2. Serial numbers
  3. Exhaust fan missing cover in ceiling.

14(F).  Liquor Storage Room
14.5.F   FIRE SEPARATION  
  Inspected  
No fire separation in rear liquor storage room.  Ceiling has been removed.


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Orillia Home Inspections
Top Table of Contents Bottom
 

Electrical Summary


Napoleon Home Inspections

Certified Building Code Official

7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255

Customer
Commercial Investor

Address
4567 Great Street to Be On
Investment City of Choice ON

The following Electrical items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

5(C).  Staff Men's Room
5.0.C   CEILING  
  Inspected  
Staff mens room had no working light.  Bulb maybe broken.

6(A).  Front Bar Area
6.11.A   ELECTRICAL DEFICIENCIES  
  Inspected  
Un-protected electrical cable on post at front entrance.

7(A).  Unit #1
7.28.A   OUTLETS AND WALL SWITCHES  
  Inspected  
Right side purple bedroom has loose outlet on front corner.

7(D).  Unit #C
7.31.D   SINK  
  Inspected  
Sink has reversed polarity at outlet.  Recommend having repaired.  Adding GFCI protection is recommended although not required.

8.  Electrical System for Building
8.1   SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS  
  Inspected  
Grounding connections in front of hydro room are corroded and loose.  Recommend replacement of clamps.
8.3   CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls)  
  Inspected  
  1. Un-used conduit in basement beside fire alarm panel.
  2.  
8.10   FIRE ALARM PANEL  
  Inspected  
Notifier 500 fire alarm panel has cover removed.  System was in trouble and indicated battery was dis-connected.
8.13   EXIT LIGHTS  
  Inspected  
Exit light at basement washroom area was not working at time of inspection.

9(A).  Hydro Room
9.1.A   WALLS  
  Inspected  
  1. Exposed wiring in junction box in hydro room
  2. Open junction box on wall.
  3. Loose light fixture.
  4. Open junction box.

14(A).  Side Office
14.7.A   ELECTRICAL DEFICIENCIES  
  Inspected  
  1. Open junction box in ceiling.
  2. Un-secured electrical wire for light switch.
  3. Extension cord material un-secured and no connector used in junction box.

14(B).  Furnace Area
14.7.B   ELECTRICAL DEFICIENCIES  
  Inspected  
  1. Un-used electrical cable with taped connections should be removed if not used. 
  2. Open junction box in ceiling.
  3. Open junction box above furnaces

14(C).  Utility Area
14.7.C   ELECTRICAL DEFICIENCIES  
  Inspected  
  1. Electrical outlet under stairs in tool area has open ground and extension cord stapled for use beside outlet.
  2. Small walkway to rear of bldg has un-secured electrical wires from outlet box.
  3. Compressor unit at rear of utility area has open junction box and exposed wiring.
  4. Open junction box in ceiling near boilers room.
  5. Un-used BX cable in ceiling of damaged drywall area.

14(E).  Walk-in Coolers
14.7.E   ELECTRICAL DEFICIENCIES  
  Inspected  
Extension cord passes through cooler to 12 v transformer in ceiling.  This is not permitted and permanent wiring should be installed.


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Orillia Home Inspections
Top Table of Contents Bottom
 

Plumbing Summary


Napoleon Home Inspections

Certified Building Code Official

7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255

Customer
Commercial Investor

Address
4567 Great Street to Be On
Investment City of Choice ON

The following Plumbing items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

4.  Plumbing System for Building
4.0   PLUMBING DRAIN, WASTE AND VENT SYSTEMS  
  Inspected  
  1. Rear alley plumbing vent does not extend above roof.
  2. Visible water leak at drain line in basement utility area at back of walkway behind pot room wall.
4.6   SUMP PUMP  
  Inspected  
Sump pump does not come on automatically.  When plugged in the pump emptied the pit but would not shut off. Float device is not working.

5(D).  Staff Ladies Room
5.4.D   SHUT OFFS FOR TAPS  
  Inspected  
One tap for sink is not working.

7(A).  Unit #1
7.18.A   COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS  
  Inspected  
Tap control unit is loose on sink in kitchen

7(B).  Unit #2
7.34.B   TOILET  
  Inspected  
Toilet is loose and should be re-secured to prevent water leakage.

9(B).  Boiler Room
9.0.B   CEILING  
  Inspected  
  1. Weil-McLain hot water boiler  -  working with no insulation on pipes.
  2. Raypak hot water boiler  - was not working and is hooked up to storage tank -  rental equipment
  3. Pressure Relief Valve is corroded and should be cleaned or replaced.
  4. Valve is broken on line from boiler storage tank.

14(B).  Furnace Area
14.2.B   FLOOR  
  Inspected  
Condensate lines for furnaces are not draining into hole in floor.  Hole in floor may not be trapped and could be source for sewer gas to enter building.

14(C).  Utility Area
14.1.C   WALLS  
  Inspected  
Sign on plumbing about previous flooding of basement.


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Orillia Home Inspections
Top Table of Contents Bottom
 

Structural Summary


Napoleon Home Inspections

Certified Building Code Official

7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255

Customer
Commercial Investor

Address
4567 Great Street to Be On
Investment City of Choice ON

The following Structural items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

7(D).  Unit #C
7.40.D   PORCHES OR DECKS  
  Inspected  
Wood steps up to unit C porch on 3rd floor have the following deficiencies:
  1. Wood steps are rotted.
  2. Supporting post is rotted at top and bottom and is not attached at base.
  3. Window has been filled in but has missing capping and no cap for vinyl siding.
  4. Exterior outlet box is loose and exposed on wall.




Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Orillia Home Inspections
Top Table of Contents Bottom
 

Heating Cooling / Summary


Napoleon Home Inspections

Certified Building Code Official

7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255

Customer
Commercial Investor

Address
4567 Great Street to Be On
Investment City of Choice ON

The following Heating and Cooling items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function or efficiency of the building. This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

9(B).  Boiler Room
9.0.B   CEILING  
  Inspected  
  1. Weil-McLain hot water boiler  -  working with no insulation on pipes.
  2. Raypak hot water boiler  - was not working and is hooked up to storage tank -  rental equipment
  3. Pressure Relief Valve is corroded and should be cleaned or replaced.
  4. Valve is broken on line from boiler storage tank.

11.  Air Conditioners
11.4   DEFICIENCIES  
  Inspected  
Insulation is missing from compressor line. Recommend adding insulation.

14(A).  Side Office
14.1.A   WALLS  
  Inspected  
Rear wall of office has exhaust fan which discharges into hallway.  This is not permitted, discharge has to go outside.

14(B).  Furnace Area
14.0.B   CEILINGS  
  Inspected  
Two KeepRite natural gas furnaces.  2005 models
  1. One furnace filter is damaged and requires replacement.
  2. Furnace closest to exit has loose ground wire from exhaust blower motor.


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Orillia Home Inspections
Top Table of Contents Bottom
 
  INVOICE

Napoleon Home Inspections
Certified Building Code Official

7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255
Inspected By:  Roger Frost - Certified Building Code Official
Inspection Date: 2020-02-20
Report ID: 1001001111110

Customer Info: Inspection Property:
Commercial Investor


Customer's Real Estate Professional:

 
4567 Great Street to Be On
Investment City of Choice ON
 

Inspection Fee:

ServicePriceAmountSub-Total
Restaurant and Apartments 900.00 1 900.00

Tax $117.00
Total Price $1017.00

Payment Method: Invoiced
Payment Status: Invoice Included with Report
Note: Mail cheque to Roger Frost, 7 Stollar Blvd, Barrie, ON L4M 6N8

Top Table of Contents Bottom
 

Inspection Agreement

This inspection was performed in accordance with and under the terms of a Pre-Inspection Agreement. The agreement was signed and agreed upon prior to the preparation of this report and a signed copy of the agreement is available upon request. An unsigned copy of the agreement may be attached to this report for your information or it may also be available on the company web site.